Description of the I/O Modules

25

EN1B-0410GE51

R0908A

Modules with Manual Overrides

The XFR822AU/XFLR822AU Analog Output Modules are
equipped with manual overrides: one rotary knob for each
analog output.
The manual overrides can be set manually to either "auto" or
"0 ─ 110%".

NOTICE

Damage to the electronic module!

Do not use a tool to adjust the rotary knobs.

Do not use excessive force. Adjust only by hand.

XFL822AU Connection Example

XFL822AU

1

73

8

11

XSL511

L

N

Umax = 11 VDC
Imax = 1 mA, -1 mA

14507287

POWER

MODULE

GND SIGNAL 24VAC

M

24V

~

Fig. 40. XFL822AU Analog Output Module

Synchronization Behavior of Analog Output Module
Configured as Floating Output

In order to regularly update the real actuator position with the
calculated position and thus ensure that the actuator
definitely reaches its end position, a synchronization process
is performed by the Analog Output Module.
During the synchronization process, the Analog Output
Module will continue running for the configured runtime once
it reaches the calculated end position.

This updating (synchronization) is performed:
• If the calculated position of the actuator

< lower synchronization threshold (2 %)
= synchronization towards 0 %

• If the calculated position of the actuator

> upper synchronization threshold (98 %)
= synchronization towards 100 %

• Following any power-up or any reset