Xl800 series power consumption, I/o modules – Honeywell XL 800 SERIES User Manual

Page 5

Advertising
background image

Excel 800

Wiring

5

EN1B-0410GE51

R0908A

XL800 Series Power Consumption

When selecting the appropriate power supply, the power
consumption of the XL800 modules must be taken into
account.

Table 3. XL800 power consumption

max. power consumption

model

24 Vac, 60 Hz

24 Vdc

XCL8010AU with
watchdog load

690 mA

640 mA

XCL8010AU without
watchdog load

190 mA

140 mA

XF821AU, XFL821AU

130 mA

80 mA

XF822AU, XFR822AU,
XFL822AU, XFLR822AU

160 mA

90 mA

XF823AU, XFL823AU

180 mA

130 mA

XF824AU, XFR824AU,
XFL824AU, XFLR824AU

140 mA

90 mA

XFR825AU

140 mA

90 mA

I/O Modules

Variants of I/O Modules
There are two variants of I/O modules:
• Panel Bus I/O modules with communication via Panel Bus

(light-gray housings)
Modules are automatically commissioned (with firmware
download) by the XCL8010AU

• L

ON

W

ORKS

Bus I/O modules (dark-gray housings) with

communication via L

ON

W

ORKS

(FTT10-A, link power

compatible) for easy integration and use with 3

rd

-party

controllers


Terminal Sockets
I/O modules are mounted on the appropriate terminal
sockets. Panel Bus I/O modules and L

ON

W

ORKS

Bus I/O

modules use the same terminal sockets.

Color Coding
To distinguish modules and components, the following color
coding is used:

Table 4. Color coding of Excel 800 Modules

color

part

red

All of the user-accessible adjustable
mechanical parts (i.e., bridge connectors and
locking mechanism) and operating controls
(manual overrides, etc.)

light-gray

Panel Bus I/O modules

dark-gray

L

ON

W

ORKS

Bus I/O modules