Troubleshooting

35

EN1B-0410GE51

R0908A

Service LED of I/O Modules

Table 43. Service LED of I/O modules

case

Service LED

meaning

remedy

1

LED remains OFF after
power-up

If the power LED is also OFF, then

– Defective

device

hardware

– Possible power supply problems, clock

problems, defective processor

► Replace hardware

2

LED is lit continuously after
first power-up

• L

ON

W

ORKS

Bus I/O modules:

– Defective

hardware

• Panel Bus I/O modules:

– I/O module has not yet been configured

by XCL8010AU

– Boot loader is active
– Failure during last firmware download
– Checksum

error

L

ON

W

ORKS

Bus I/O modules:

► Replace hardware
Panel Bus I/O modules:
► Set the hex address to the position configured

with CARE

► Ensure that I/O Bus switch S2 of XCL8010AU is

set to position "Panel"

► Check the Panel Bus wiring:

- Check for cable breaks
- Check for cable short-circuits
- If using separate transformers: Check ground

connection

► Eliminate any mixture of Panel Bus I/Os and

LonWorks I/Os on same wire

► Allow XCL8010AU to configure I/O module
► Unplug and replug the module
► If problem persists, replace hardware

3

Alternating flash between
service LED and power LED

Panel Bus I/O modules, only:
Download error or application checksum error.
Boot loader is running

► Panel Bus I/O modules, only:

Wait until rebooting (firmware download) has
been completed

4

LED flashes at power up,
goes OFF, and then is lit
continuously

L

ON

W

ORKS

Bus I/O modules, only:

L

ON

W

ORKS

Bus I/O module lacks application

► Download application

5

LED repeatedly blinks
ON for 1 sec and
OFF for 1 sec

L

ON

W

ORKS

Bus I/O modules, only:

L

ON

W

ORKS

Bus I/O module is unconfigured, but

has an application

► Set module to configured mode

6

LED remains OFF after a
short ON duration

I/O module is configured and running normally

No action necessary

7

LED flashes continuously in
following pattern:
4 x ON/OFF followed by
pause

Sensor failure of Analog Input Module
(in case of L

ON

W

ORKS

Bus I/O modules, this

behavior can occur only if the appropriate NV
has been bound)

► Check sensor or connection
► Check sensor configuration

8

LED flashes continuously in
following pattern:
5 x ON/OFF followed by
pause

L

ON

W

ORKS

Bus I/O modules, only: L

ON

W

ORKS

I/O Bus module has received the wink
command from network, physical outputs are
unaffected

No action necessary

9

LED flashes continuously in
following pattern:
6 x ON/OFF followed by
pause

Boot loader problem or hardware defect

► Replace hardware

10

LED flashes continuously in
following pattern:
7 x ON/OFF followed by
pause

Communications failure

► Check bus wiring
► Ensure that I/O Bus switch S2 of XCL8010AU is

set to correct position

► Ensure that L

ON

W

ORKS

Bus I/O modules and

Panel Bus I/O modules are not sharing same
bus

► In case of Panel Bus I/O modules, only:

Check for incorrect HEX addresses (2 Panel Bus
I/O modules using same HEX address)

► In case of L

ON

W

ORKS

Bus I/O modules, only:

Check heartbeat