Binary input modules, Types of binary input modules, Features – Honeywell XL 800 SERIES User Manual

Page 26: Terminals, Technical data

Advertising
background image

Description of the I/O Modules

Excel 800

EN1B-0410GE51 R0908A

26

Binary Input Modules

Types of Binary Input Modules

Table 30. Excel 800 Binary Input Modules

type

description

housing

XF823

Panel Bus Binary Input Module

light-gray

XFL823

L

ON

W

ORKS

Bus Binary Input

Module

dark-gray

XS823 terminal

socket

light-gray

Features

• 12 binary inputs
• 12 configurable status LEDs (green/red, yellow/OFF)
• Binary inputs can be used as

– Static digital inputs as dry-contacts

Fig. 41. XF823AU Binary Input Module with terminal

socket

Legend
1 Service button S1
2 Hex switch S2
3 Input LEDs
4 Service LED
5 Power LED

Functionality of service LED and power LED: see Table 42
and following.

Terminals

BI12

12

25 26

74

78

73

77

72

76

71

75

24

V~

24

V~

24

V~0

24

V~0

COM

B

COM

B

COM

A

COM

A

BI11

11

BI10

10

BI9

9

BI8

8

BI7

7

BI6

6

BI5

5

BI4

4

BI3

3

BI2

2

BI1

1

24

23

22

21

20

19

18

17

16

15

14

GND

13

GND GND GND GND GND GND GND GND GND GND GND

Fig. 42. Terminal assignment and internal connections of

Binary Input Modules

Table 31. Description of Binary Input Module terminals

ter-

minal

signal

comment

71, 75

COM a

2-wire communication bus (LON/Panel
Bus)

72, 76

COM b

2-wire communication bus (LON/Panel
Bus)

73, 77

24 V~

Power supply

74, 78

24 V~0

Power supply

1 ─ 12 BI1 ─ BI12 Binary inputs 1 ─ 12

13 ─

24

GND

Ground. All grounds are connected
internally to each other.

25, 26

Shield connection (functional earth),
internally connected to the DIN rail.


NOTE:

Shield connection to be used for shielded I/O
cables only. It is not allowed to connect a
L

ON

W

ORKS

shield.

Technical Data

Table 32. Technical data for of Binary Input Modules

input type

dry-contact

current rating (closed
input)

2 mA

open contact voltage

16 ─ 22 VDC

Advertising