Excel 800

Description of the I/O Modules

21

EN1B-0410GE51

R0908A

C-Bus Termination Switch S1

The XCL8010AU

Controller Module features a 3-position C-

Bus termination switch S1.
This switch must be set in accordance with the given C-Bus
configuration.

Fig. 34. C-Bus termination switch

Table 21. XCL8010AU

C-Bus termination switch S1

settings

switch setting

S1

baud rate

9.6k all

Up to 9600 baud (default setting)

76k mid

Up to 76800 baud without bus termination

76k end

Up to 76800 baud with bus termination
controller at the end of the C-Bus

Memory

Table 22. XCL8010AU memory

memory

size

usage

SRAM 512

KB

For controller application,
modem trend and firmware
RACL application: 128 KB
Total application: 192 KB

Flash 2

MB

Firmware (1 MB) and application
(1 MB) storage

EPROM

128 KB For bootstrap loader


NOTE: The

XCL8010AU

Controller Module does not

contain a battery. RAM (data and realtime
clocktime) is buffered for 3 days by a super
capacitor.

Description of the I/O Modules

Common Features

Switches Located on the Terminal Socket

Table 23. Terminal socket switches

feature

function

Service button
S1

• LED test, see section "Troubleshooting"

on page 31

• L

ON

W

ORKS

service button functionality

for L

ON

W

ORKS

Bus I/O modules

Hex switch S2

• Module addressing for Panel Bus

I/O modules


LEDs Located on the I/O Module

Table 24. LEDs on I/O module

feature

function

Service LED
(yellow)

• Service information, see section

"Troubleshooting" on page 31

Power LED
(green)

• Information on power supply, see section

"Troubleshooting" on page 31


For the location of these elements, see figures of the
respective modules.