REmotE tHERmoStat anD Low VoLtagE ContRoL

CONNeCTIONS

Remote Thermostat

To control the unit with a wall-mounted thermostat:

1) Pull the disconnect switch.
2) Unscrew and remove the control box panel.
3) After selecting which side you want to run your thermostat

wire through, run the wires through the side hole in the box

to reach the connection terminal for the wiring.
4) Make the wire connections, appropriately matching the

wires as shown in the wiring diagram.
5) Once each wire is matched and connected, the unit is now

controlled by the thermostat.
6) Reattach the control box cover.

RT5 (Two speed fan)

RT4 (One speed fan)

Cool Off Heat

Auto On

All Friedrich Vert-I-Pak units are factory configured to be

controlled by using a 24V single stage remote wall mounted

thermostat. The thermostat may be auto or manual changeover

as long as the control configuration matches that of the

Vert-I-Pak unit.

NOTE: An improperly operating, or poorly located room

thermostat can be the source of perceived equipment

problems. A careful check of the thermostat and wiring

must be made then to insure that it is not the source of

problems.

Manual Changeover Thermostat

For Heat Pump equipped units: a single stage, heat/cool

thermostat with a terminal for a reversing valve operation is

required. Terminal “B” should be continuously energized in the

heat mode and terminal “G” should be energized whenever

there is a call for heating or cooling. (Typically, a single stage,

heat/cool thermostat designed for use with electric heat

systems will meet the above requirements).

Location

The thermostat should not be mounted where it may be

affected by drafts, discharge air from registers (hot or cold),

or heat radiated from the sun or appliances.
The thermostat should be located about 5 Ft. above the

fl oor in an area of average temperature, with good air

circulation. Close proximity to the return air grille is the

best choice.

Mercury bulb type thermostats MUST be level to control

temperature accurately to the desired set-point. Electronic

digital type thermostats SHOULD be level for aesthetics.

Thermostat Location