VPak ELECtRonIC ContRoL BoaRD anD waLL

tHERmoStat SEqUEnCE oF oPERatIon

Wall Thermostat Connections:

• The control is compatible with a standard single stage heat and cool Wall

Thermostat.

• It is compatible with Friedrich

RT4 and RT5 Wall thermostats.

• Terminals are:

C – Common ground terminal.

W – call for heating.

Y – call for cooling,

R – 24V power from Electronic control to Wall Thermostat.

GL - call for low Fan.

GH- call for high fan

B – call for heat pump reversing valve.

The outputs of a single stage Heat and Cool Wall thermostat:

• When a call for

cool from Wall thermostat the signals will go to

terminal

Y, GL or GH.

• When a call for

heat from Wall thermostat the signals will go to

terminal

W, B, GL or GH.

• When a call for Fan Only from Wall thermostat the signals will go

to terminal

GL or GH.

Remote T-stat Operation Features:

All buttons on the electronic control board will be disabled except “Heat”

When power is applied to L1 and L2, the Power LED will be lit on the

electronic control.

and “High Fan” buttons during Error code mode operation.

COMMON CONTROL FEATURES FOR COOL WITH ELECTRIC HEAT

AND HEAT PUMP WITH ELECTRIC HEAT UNITS:

Power On and Off Features on the Electronic Control:

Temperature set:

This feature will depend on Wall Thermostat.

˚F/˚C set:

This feature will depend on Wall Thermostat.

Fan speed, fan cycle on/off or continuous operation

This feature will depend on Wall Thermostat. For single speed Wall

Thermostat, user needs to choose between

GH terminal (High Fan) or

GL terminal (Low Fan). For a two speed fan Wall Thermostat, connect

both

GL and GH. If the PCB receives signals for both GL and GH at the

same time, only

High Fan turns on.