Warning, Testing the coil, Checking the reversing valve – Friedrich 9 User Manual

Page 34

Advertising
background image

32

Reversing Valve in Heating Mode

tEStIng tHE CoIL

The solenoid coil is an electromagnetic type coil mounted

on the reversing valve and is energized during the

operation of the compressor in the heating cycle.

1. Turn off high voltage electrical power to unit.
2. Unplug line voltage lead from reversing valve coil.
3. Check for electrical continuity through the coil. If you

do not have continuity replace the coil.

4. Check from each lead of coil to the copper liquid line

as it leaves the unit or the ground lug. There should

be no continuity between either of the coil leads

and ground; if there is, coil is grounded and must be

replaced.

5. If coil tests okay, reconnect the electrical leads.
6. Make sure coil has been assembled correctly.
NOTE: Do not start unit with solenoid coil removed from

valve, or do not remove coil after unit is in operation. This

will cause the coil to burn out.

CHECkIng tHE REVERSIng VaLVE

NOTE: You must have normal operating pressures before

the reversing valve can shift.

Check the operation of the valve by starting the system

and switching the operation from “Cooling” to “Heating”

and then back to “Cooling”. Do not hammer on valve.
Occasionally, the reversing valve may stick in the heating

or cooling position or in the mid-position.
When sluggish or stuck in the mid-position, part of the

discharge gas from the compressor is directed back to the

suction side, resulting in excessively high suction pressure.

Should the valve fail to shift from coooling to heating, block

the air flow through the outdoor coil and allow the discharge

Reversing Valve in Cooling Mode

ELECTRIC SHOCK HAZARD

WARNING

Unplug and/or disconnect all electrical power

to the unit before performing inspections,

maintenances or service.

Failure to do so could result in electric shock,

serious injury or death.

Sealed Refrigeration System contains refrigerant

and oil under high pressure.

Proper safety procedures must be followed,

and proper protective clothing must be worn

when working with refrigerants.

Failure to follow these procedures could

result in serious injury or death.

WARNING

HIGH PRESSURE HAZARD

pressure to build in the system. Then switch the system

from heating to cooling.

If the valve is stuck in the heating position, block the air

flow through the indoor coil and allow discharge pressure

to build in the system. Then switch the system from

heating to cooling.

Should the valve fail to shift in either position after

increasing the discharge pressure, replace the valve.

Dented or damaged valve body or capillary tubes can

prevent the main slide in the valve body from shifting.

If you determing this is the problem, replace the reversing

valve.

After all of the previous inspections and checks have

been made and determined correct, then perform the

“Touch Test” on the reversing valve.

Advertising