Electrical troubleshooting chart - cooling 24k btu, No cooling operation – Friedrich 9 User Manual

Page 43

Advertising
background image

ELECtRICaL tRoUBLESHootIng CHaRt - CooLIng

24k BtU

Yes

No

24V at t-stat and

control wiring?

Yes

No

24V at t-stat and

control wiring?

NO COOLING OPERATION

Before continuing

check for Error

Codes, see

electronics control

diagnostics and

test mode, page 15

Yes

Yes

Compressor outdoor

fan motor and indoor

blower should now

operate

See Refrigerant Circuit

diagnosis if unit still is

not cooling properly

Indoor blower runs but

outdoor fan motor and

compressor do not run

Compressor and outdoor

fan motor run but indoor

blower does not run

Set thermostat to

"Cool," move the Temp.

lever below the present

Room Temp.

Nothing operates,

entire system

appears dead

Line voltage present

at the Transformer

Primary

Problems indicated with

Room Thermostat or

Control Wiring

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

No

O.K.

No

Is Line Voltage present

at Motor Leads?

Check Capacitor, is

Capacitor Good?

Replace Capacitor

Motor should run

Possible motor

problem indicated.

Check motor

thoroughly

Yes

Yes

Yes

No

No

No

Supply Circuit

problems, loose

Connections, or bad

Relays/Board

Replace Capacitor

and/or Start Assist

Device

Allow ample time

for pressures to

equalize

Possible Compressor

problem indicated.

See Compressor

Checks

Is Locked Rotor

Voltage a minimum of

197 Volts?

Are Capacitor and (if

so equipped) Start

Assist good?

Have System

Pressures Equalized?

Compressor should

run

Yes

Yes

No

No

No

No

Yes

Compressor and

outdoor fan motor

should now operate

See Refrigerant

Circuit Diagnosis

if unit still is not

cooling properly

Yes

Insure that Fuses

are good and/or that

Circuit Breakers are

on and voltage is 208/230

O.K.

208/230 Volts present

at #1 relay and “OD”

terminal on board?

208/230 Volts present

at compressor’s

contactor?

Problems indicated

in Blower Relay

of board

Replace board

Check Supply Circuit’s

jumper at transformer. If

okay, replace board

24 Volts at

“R” Terminal on board

24 Volts present at

Y terminals on

t-stat and board?

Problems indicated with

Control Transformer

replace board

Defective t-stat

defective control wiring

or transformer

Check contactor

If defective replace

41