No cooling operation – Friedrich 9 User Manual

Page 42

Advertising
background image

ELECtRICaL tRoUBLESHootIng CHaRt - CooLIng

9k BtU, 12k BtU, & 18k BtU

NO COOLING OPERATION

Insure that Fuses

are good and/or that

Circuit Breakers are

on and voltage is 208/230

Compressor and Fan

Motor should now

operate

See Refrigerant Circuit

diagnosis if unit still is

not cooling properly

Fan runs but

Compressor doesn't

Compressor runs but

Blower/Fan doesn't

Set thermostat to

"Cool," and the Temp.

below the present

Room Temp.

Nothing operates,

entire system

appears dead

Line voltage present

at the Transformer

Primary

24 Volts present at

208/230 Volts present

at #1 relay on board?

Y terminals on

t-stat and board?

Problems indicated with

Room Thermostat or

Control Wiring

Replace board

Problems indicated

in Blower Relay

of board

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No

No

No

O.K.

O.K.

No

Is Line Voltage present

at Motor Leads?

Check Capacitor, is

Capacitor Good?

Replace Capacitor

Motor should run

Possible motor

problem indicated.

Check motor

thoroughly

Yes

Yes

No

No

No

Supply Circuit

problems, loose

Connections, or bad

Relays/Board

Replace Capacitor

and/or Start Assist

Device

Allow ample time

for pressures to

equalize

Possible Compressor

problem indicated.

See Compressor

Checks

Is Locked Rotor

Voltage a minimum of

197 Volts?

Are Capacitor and (if

so equipped) Start

Assist good?

Have System

Pressures Equalized?

Compressor should

run

Yes

Yes

No

No

No

No

Yes

Compressor and fan

motor should now

operate

See Refrigerant

Circuit Diagnosis if

unit still is not cooling

properly

Yes

Yes

No

Check Supply Circuit’s

jumper at transformer. If

okay, replace board

24 Volts at

“R” Terminal on board

Before continuing

check for Error

Codes, see

electronics control

diagnostics and

test mode, page 15

24V at t-stat and

control wiring?

Defective t-stat

defective control wiring

or transformer

Problems indicated with

Control Transformer

replace board

40

Advertising