Warning – Friedrich 9 User Manual

Page 37

Advertising
background image

35

Single Phase Resistance test

Remove the leads from the compressor terminals and set

the ohmmeter on the lowest scale (R x 1).

Touch the leads of the ohmmeter from terminals common

to start (“C” to “S”). Next, touch the leads of the ohmmeter

from terminals common to run (“C” to “R”).

Add values “C” to “S” and “C” to “R” together and

check resistance from start to run terminals (“S” to “R”).

Resistance “S” to “R” should equal the total of “C” to “S”

and “C” to “R.”

In a single phase PSC compressor motor, the highest

value will be from the start to the run connections (“S” to

“R”). The next highest resistance is from the start to the

common connections (“S” to “C”). The lowest resistance

is from the run to common. (“C” to “R”) Before replacing a

compressor, check to be sure it is defective.

GROUND TEST

Use an ohmmeter set on its highest scale. Touch one

lead to the compressor body (clean point of contact as

a good connection is a must) and the other probe in turn

to each compressor terminal. If a reading is obtained the

compressor is grounded and must be replaced.

Check the complete electrical system to the compressor

and compressor internal electrical system, check to be

certain that compressor is not out on internal overload.

Complete evaluation of the system must be made

whenever you suspect the compressor is defective. If

the compressor has been operating for sometime, a

careful

examination must be made to determine why the

compressor failed.

Many compressor failures are caused by the following

conditions:
1. Improper air flow over the evaporator.

2. Overcharged refrigerant system causing liquid to be

returned to the compressor.

3. Restricted refrigerant system.

4. Lack of lubrication.

5. Liquid refrigerant returning to compressor causing oil

to be washed out of bearings.

6. Noncondensables such as air and moisture in

the system. Moisture is extremely destructive to a

refrigerant system.

7. Capacitor test (see page 21).

CHECKING COMPRESSOR EFFICIENCY
The reason for compressor inefficiency is normally due

to broken or damaged suction and/or discharge valves,

reducing the ability of the compressor to pump refrigerant

gas.
This condition can be checked as follows:
1. Install a piercing valve on the suction and discharge or

liquid process tube.

2. Attach gauges to the high and low sides of the system.

3. Start the system and run a “cooling or heating perfor-

mance test.” If test shows:

A.

Below normal high side pressure

B.

Above normal low side pressure

C.

Low temperature difference across coil

The compressor valves are faulty - replace the

compressor.

ELECTRIC SHOCK HAZARD

WARNING

Turn off electric power before service or

installation. Extreme care must be used, if it

becomes necessary to work on equipment

with power applied.

Failure to do so could result in serious injury or

death.

Advertising