Electronic control configuration, Factory dip switch configuration, Room freeze protection – switch 6 – Friedrich 9 User Manual

Page 16: Emergency heat override – switch 7, Discharge air sensor override – switch 8, Error code diagnostics, Button location for vert-i-pak models

Advertising
background image

14

Low fan

High fan

Fan only

Power

Temp

Temp

Cool

Heat

1 2 3 4 5 6 7 8

O

N

Electronic Control Configuration

The adjustable control dip switches are located at the lower

left hand portion of the digital Smart Center. The inputs are

only visible and accessible with the front cover removed from

the Unit.

Factory Dip Switch Configuration

Dip Switch Setting
Switches 1-4 ON
Switch 5-7 OFF
Switch 8 ON

Room Freeze Protection – Switch 6

Units are shipped from the factory with the room freeze protec-

tion disabled. Room Freeze Protection can be switched on at

the owner’s preference by moving Dip Switch 6 to ‘ON’. This

feature will monitor the indoor room conditions and in the event

that the room falls below 40°F the unit will cycle on high fan with

the electric heater. This occurs regardless of mode.

Emergency Heat Override – Switch 7

Units are shipped from the factory with the room emergency

heat override disabled. In the unlikely event of a compressor

failure a heat pump unit may be switched to operate in only the

electric heat mode until repairs can be made, by moving Dip

Switch 7 to ‘ON’.

Discharge Air Sensor Override – Switch 8

This switch MUST remain in the “ON” position for Vert-I-Pak

models, since they do not use a discharge air sensor. If the

switch is positioned in the “OFF” position on these models it

will result in the erroneous display Error Code 14 indicating that

the Discharge air temperature sensor is open or shorted.

Note: In order for the control to recognize “Dip” switch

setting changes, the unit must be disconnected

from power supply when making any configuration

changes.

Error Code Diagnostics

The VPAK electronic control continuously monitors the Vert-I-Pak

unit operation and will store error codes if certain conditions

are witnessed. In some cases the unit may take action and shut

the unit off until conditions are corrected.
To access the error code menu press the ‘

HEAT’ and ‘HIGH

FAN’ buttons simultaneously for three seconds. If error codes

are present they will be displayed. If multiple codes exist you

can toggle between error codes using the

temp up ▲ button. To

clear all codes press the

temp down ▼ button for three seconds

while in the error code mode. To exit without losing codes

press the ‘Low Fan’ button.

Button Location for Vert-I-Pak Models

With the remote thermostat escutcheon installed, the button

locations to access the diagnostics mode can be located as

shown below.

Electronic Control Error Code

Diagnostics and Test Mode

* Heat and high fan - access error codes

* Temp up ▲ and temp down ▼ - toggle between error codes

* Low fan - exit error code mode without losing stored error

codes.

* Temp down ▼ - clears all error codes

NOTE: Hold buttons down for three seconds.