Warning – Friedrich 9 User Manual

Page 30

Advertising
background image

Undercharged Refrigerant Systems

An undercharged system will result in poor performance

(low pressures, etc.) in both the heating and cooling

cycle.
Whenever you service a unit with an undercharge of

refrigerant, always suspect a leak. The leak must be

repaired before charging the unit.
To check for an undercharged system, turn the unit on,

allow the compressor to run long enough to establish

working pressures in the system (15 to 20 minutes).
During the cooling cycle you can listen carefully at the exit

of the metering device into the evaporator; an intermittent

hissing and gurgling sound indicates a low refrigerant

charge. Intermittent frosting and thawing of the evaporator

is another indication of a low charge, however, frosting

and thawing can also be caused by insufficient air over

the evaporator.
Checks for an undercharged system can be made at

the compressor. If the compressor seems quieter than

normal, it is an indication of a low refrigerant charge.

overcharged Refrigerant Systems

A check of the amperage drawn by the compressor

motor should show a lower reading. (Check the Unit

Specification.) After the unit has run 10 to 15 minutes,

check the gauge pressures. Gauges connected to system

with an undercharge will have low head pressures and

substantially low suction pressures.

of the evaporator will not be encountered because the

refrigerant will boil later if at all. Gauges connected to

system will usually have higher head pressure (depending

upon amount of over charge). Suction pressure should be

slightly higher.

Compressor amps will be near normal or higher.

Noncondensables can also cause these symptoms. To

confirm, remove some of the charge, if conditions improve,

system may be overcharged. If conditions don’t improve,

Noncondensables are indicated.
Whenever an overcharged system is indicated, always

make sure that the problem is not caused by air flow

problems. Improper air flow over the evaporator coil may

indicate some of the same symptoms as an over charged

system.
An overcharge can cause the compressor to fail, since it

would be “slugged” with liquid refrigerant.
The charge for any system is critical. When the compressor

is noisy, suspect an overcharge, when you are sure that

the air quantity over the evaporator coil is correct. Icing

ELECTRIC SHOCK HAZARD

WARNING

Turn off electric power before service or

installation.

Extreme care must be used, if it becomes

necessary to work on equipment with power

applied.

Failure to do so could result in serious injury or

death.

Sealed Refrigeration System contains refrigerant

and oil under high pressure.

Proper safety procedures must be followed,

and proper protective clothing must be worn

when working with refrigerants.

Failure to follow these procedures could

result in serious injury or death.

WARNING

HIGH PRESSURE HAZARD

28

Advertising