Warning, Components testing (continued) – Friedrich 9 User Manual

Page 25

Advertising
background image

DRAIN PAN VALVE

During the cooling mode of operation, condensate which

collects in the drain pan is picked up by the condenser fan

blade and sprayed onto the condenser coil. This assists

in cooling the refrigerant plus evaporating the water.

During the heating mode of operation, it is necessary that

water be removed to prevent it from freezing during cold

outside temperatures. This could cause the condenser

fan blade to freeze in the accumulated water and prevent

it from turning.

To provide a means of draining this water, a bellows type

drain valve is installed over a drain opening in the base

pan.

This valve is temperature sensitive and will open when

the outside temperature reaches 40°F. The valve will

close gradually as the temperature rises above 40°F to

fully close at 60°F.

TESTING THE HEATING ELEMENTS AND

LIMIT SWITCHES

Testing of the heating elements can be made with an

ohmmeter or continuity tester across the terminals after

the power wires have been removed. Test the limit switch

for continuity across its input and output terminals.Test

below the limit switch’s reset temperature.

HEATER ELEMENTS AND LIMIT SWITCHES’

SPECIFICATIONS

All heat pumps and electric heat models are equipped

with a heating element and a limit switch (bimetal ther-

mostat). The limit is in series with the element and will

interrupt the power at a designed temperature.

Should the blower motor fail, filter become clogged or air-

flow be restricted etc., the high limit switch will open and

interrupt the power to the heater before reaching an un-

safe temperature condition.

VPAK 9K, 12K and 18K BTUs Models:

2.5 KW, 230 V, Resistance 18.61 Ohms + - 5%.

Has 1 Limit Switch, Opens at

120° F, Closes at 90° F,

It has a One Time Open Temp. of

145° F.

3.4 KW, 230 V, Resistance 13.68 Ohms + - 5%.

Has 1 Limit Switch, Opens at

120° F, Closes at 90° F,

It has a One Time Open Temp. of

145° F.

5 KW, 230 V, Resistance 9.31 Ohms + - 5%.

Has 1 Limit Switch, Opens at

130° F, Closes at 100° F,

It has a One Time Open Temp. of

155° F.

VPAK 24K BTUs Models:

2.5 KW, 230 V, Resistance 18.61 Ohms + - 5%.

Has 2 Limit Switches, Primary Opens at

155° F,

Closes at

125° F, Secondary’s Open Temp. is 200° F.

3.4 KW, 230 V, Resistance 13.68 Ohms + - 5%.

Has 2 Limit Switches, Primary Opens at

155° F,

Closes at

125° F, Secondary’s Open Temp. is 200° F.

5 KW, 230 V, Resistance 9.31 Ohms + - 5%.

Has 2 Limit Switches, Primary Opens at

155° F,

Closes at

125° F, Secondary’s Open Temp. is 200° F.

7.5 KW, 230 V (composed of 2, 3.7 KW Elements)

Each Has a Resistance of

12.41 Ohms + - 5%.

Each Has 2 Limit Switches, Primary Opens at

165° F,

Closes at

135° F With a 1 time Open Temp. of 210° F.

Secondary Limit’s Open Temp. is

200° F.

10 KW, 230 V (composed of 2, 5 KW Elements)

Each Has a Resistance of

9.31 Ohms + - 5%.

Each Has 2 Limit Switches, Primary Opens at

165° F,

Closes at

135° F With a 1 time Open Temp. of 210° F.

Secondary Limit’s Open Temp. is

200° F.

NOTE: Always replace with an exact replacement.


Bellows Assembly
Drain Pan Valve

ComPonEntS tEStIng (Continued)

ELECTRIC SHOCK HAZARD

WARNING

Disconnect power to the unit before

servicing. Failure to follow this warning

could result in serious injury or death.

23