Expansion modules, 1expansion modules – FANUC Robotics America GFK-1535A User Manual

Page 17

Advertising
background image

GFK-1535A

Chapter 1 Introduction

1-13

1

Expansion Modules

Expansion modules can be used to extend the I/O Station and add more modules.
There are two basic types of VersaMax I/O expansion systems, Multi-Rack and
Two-Rack Local:

S

Multi-Rack: A VersaMax PLC or NIU I/O Station with an Expansion
Transmitter Module (IC200ETM001) and one to seven expansion “racks”, each
with an Expansion Receiver Module (IC200ERM001 or IC200ERM002). If all
the Expansion Receivers are the Isolated type (IC200ERM001), the maximum
overall cable length is 750 meters. If the expansion bus includes any non-
isolated Expansion Receivers (IC200ERM002), the maximum overall cable
length is 15 meters.

PS

CPU/NIU

PS

ERM

PS

ERM

ETM

VersaMax ExpansionRack 1

Terminator

Plug

15M with any

IC200ERM002 ERMs

750M with all

IC200ERM001 ERMs

VersaMax PLC or I/O Station Main Rack (0)

VersaMax ExpansionRack 7

IC200CBL601,

602, 615

S

Two-Rack Local: A PLC or NIU I/O Station connected directly to one
expansion rack with non-isolated Expansion Receiver Module
(IC200ERM002). Maximum cable length is 1 meter.

PS

ERM

VersaMax Expansion Rack

1 M

VersaMax PLC or NIU I/O Station Main Rack

PS

CPU/NIU

IC200CBL600

Advertising