Connecting the Expansion Cable: Single-ended

For a system with one non-isolated expansion rack (IC200ERM002) and NO
Expansion Transmitter, connect the expansion cable from the serial port on the
VersaMax NIU to the Expansion Receiver as shown below. The maximum cable
length is one meter. Cables cannot be fabricated for this type of installation; cable
IC200CBL600 must be ordered separately. Note: Do not disconnect an expansion
cable while the system is operating. It will cause momentary disruptions in bus
communications.

PS

ERM

VersaMax Expansion Rack

1 M

VersaMax PLC or NIU I/O Station Main Rack

PS

CPU/NIU

No Terminator Plug is needed in a single-ended installation; however, it will not
impede system operation if installed.

Single-Ended Inter-Rack Connection (IC200CBL600)

PIN

1
2
3
6
9
10
12
16
14

0V
T_IOCLK
T_RUN
T_IODT_
T_RERR
T_RIRQ_
T_FRAME
T_RSEL
0V

PIN

16-PIN

MALE

16-PIN

FEMALE

26-PIN

MALE

26-PIN

FEMALE

15

16

1

2

4
7
22
14
18
15
11
10
19
23

1

SINGLE_
0V
T_IOCLK
T_RUN
T_IODT_
T_RERR
T_RIRQ_
T_FRAME
T_RSEL
0V

SHIELD

1 M

Expansion

Receiver

IC200ERM002

Receiving

Port

VersaMax

CPU or NIU

Serial Port

Power Sources for Single-Ended Expansion Rack Systems

When operating the system in single-ended mode, the power supplies for the main
rack and expansion rack must be fed from the same main power source. The main
rack and expansion racks cannot be switched ON and OFF separately; either both
must be ON or both must be OFF for proper operation.

Power for module operation comes from the Power Supply installed on the
Expansion Receiver Module. If the expansion rack includes any Power Supply
Booster Carrier and additional rack Power Supply, it must be tied to the same
source as the Power Supply on the Expansion Receiver Module.