5-6

VersaMax™ System Genius® Network Interface Unit User's Manual – November 2000

GFK-1535A

5

Configuration Data

Datagrams can be used to read and write configuration data for an I/O Station.
However, most systems will instead use the Remote I/O Manager or VersaPro
software for configuration.

For a Network Interface Unit, the configuration data specifies the “rack” and slot
number of a specific device in the station. The length specified must exactly match
the length of the configuration data for the module (Network Interface Unit or other
module in the I/O station); partial configuration data cannot be read or written. For
programming instructions, you should refer to the documentation set for the PLC.

Configuration files for conventional I/O modules can be read or written one module
per message. However, the configuration files of intelligent modules may exceed
the 128-byte maximum length of a Genius message. Therefore, any Write
Configuration to an intelligent module must be contained within a Begin/End
Packet Sequence.

Read Configuration Data

Subfunction Code: 02 hex

The Read Configuration Datagram is used to read configuration data from the NIU.

Read Configuration Data Format

Byte #

Description

0

Rack Number (0,…, 7)

1, 2

Length (must match the length for the specific device whose configuration will be
written. Maximum=128)

3

Slot (0,…, 9.

Note that in datagrams, the slot numbering is different that the

number described elsewhere in the manual. In datagrams only: Power Supplies and
Carriers are “slot” 0

Network Interface Unit or
Expansion Receiver Module is “slot” 1)
Modules are “slots” 2-9

4, 5

Offset into slot configuration data, used to read module configuration data that is
greater than 64 words in length