2-14

VersaMax™ System Genius® Network Interface Unit User's Manual – November 2000

GFK-1535A

2

Overriding a Network Configuration

The NIU can also be configured via a message from the network. A network
configuration can be set up to deliberately disable the auto-configuration function.
If autoconfiguration has previously been disabled by a network configuration, you
can restore the autoconfiguration function by following the steps below.

1.

Set the upper SBA select switch (SBAx10) on the NIU to the A position.

0

1

0

0

7

6

4

5

8

9

1

1

BAUD
RATE

SBA

X10

3

2

3

2

3

2

SBA
X1

N

N

A

U

A: Autoconfigure NIU (override
network configuration)

2.

Cycle power.

3.

Reset the upper SBA switch to select the tens digit of the SBA.

4.

Cycle power again.

Changing the SBA to a normal SBA does not disable autoconfiguration again. Once
autoconfiguration has been enabled, it cannot be disabled manually. A configuration
message sent to the NIU over the network or from the Remote I/O Manager
configuration tool disables autoconfiguration.

Reenabling Network Configuration

To reenable a network configuration that has been overridden as described above:

1.

Set the SBA select switches on the NIU to a valid address between 0 and 31.

2.

Cycle power.

Upgrading the NIU Firmware

1

.

Connect the cable (IC200CBL002) from the programming device to the port
on the lefthand side of the NIU.

2

.

Set the upper switch (SBAx10) to the U (Upload) position.

0

1

0

0

7

6

4

5

8

9

1

1

BAUD
RATE

SBA

X10

3

2

3

2

3

2

SBA
X1

N

N

A

U

U: Power up in bootloader mode

3

.

Cycle power to the NIU. The NIU will power up in bootloader mode.

4.

Follow the instructions supplied with the upgrade to transfer new NIU firmware
to the NIU.