Chapter 10

Fan Modules Replacement

10-7

10.1.5

Accessing the 172-mm Fan Module

1. From the XSCF Shell prompt, use the replacefru command to disable the fan

to be removed.

The replacefru command is menu-driven. replacefru will continue while the
fan is removed and then test the fan. Refer to

Section 4.3.1, “Removing and Replacing

a FRU” on page 4-7

for more information.

Caution –

To prevent the equipment rack from tipping over, you must deploy the

antitilt feature, if applicable, before you slide the server out of the equipment rack.

Note –

When drawing out the M4000/M5000 Server to the front, release the cable tie

holding the PCI cables on the rear of the server.

2. Deploy the rack’s antitilt features (if applicable) and slide the server out of the

equipment rack.

See

Section 5.1.1, “Sliding the Server Out of the Equipment Rack” on page 5-2

.

Caution –

Use proper ESD grounding techniques when handling components. See

Section 1.1, “Safety Precautions” on page 1-1

.

XSCF> replacefru