2 installing the operator panel, 3 securing the server, Installing the operator panel – FUJITSU M5000 User Manual

Page 255: Securing the server

Advertising
background image

Chapter 15

Operator Panel Replacement

15-7

15.2.2

Installing the Operator Panel

Caution –

Use proper ESD grounding techniques when handling components. See

Section 1.1, “Safety Precautions” on page 1-1

.

1. Place the operator panel keyholes over the guide pins and gently push the

operator panel towards the front of the server.

If the operator panel will not move forward, gently adjust where the light pipes at
the front of the operator panel fit into the sockets at the front of the server.

2. Tighten the captive screw that holds the operator panel in place.

3. Connect the operator panel keyswitch cable.

4. Connect the operator panel signal cable.

15.2.3

Securing the Server

1. Slide the server into the equipment rack and secure the stabilizer bar.

See

Section 5.1.2, “Sliding the Server Into the Equipment Rack” on page 5-4

.

2. Install the fan cage and tighten the three (3) captive screws to secure it in place.

The SPARC Enterprise M4000 server uses only two (2) captive screws.

3. Install the 172-mm fan units.

See

Section 10.1.7, “Installing the 172-mm Fan Module” on page 10-9

.

4. Power on the server.

This step includes reconnecting power cables, verifying the state of the LEDs, and
turning the keyswitch to the Locked position. See

Section 4.4.2, “Powering the

Server On Using Software” on page 4-13

.

5. Use the showhardconf command to confirm that the new component is

installed.

Refer to

Section 4.3.2, “Verifying Hardware Operation” on page 4-9

for more

information.

XSCF> showhardconf

Advertising
This manual is related to the following products: