14-4

SPARC Enterprise M4000/M5000 Servers Service Manual • December 2010

Caution –

Use proper ESD grounding techniques when handling components. See

Section 1.1, “Safety Precautions” on page 1-1

.

2. Remove the I/O unit.

Removing the I/O unit includes multiple steps such as removing labelling and
disconnecting the cables, removing the PCI cassettes, and disconnecting the cable
management arm. See

Section 8.3.2, “Removing the I/O Unit” on page 8-10

.

3. Remove the XSCF unit.

See

Section 9.1.2, “Removing the XSCF Unit” on page 9-4

.

Caution –

To prevent the equipment rack from tipping over, you must deploy the

antitilt feature, if applicable, before you slide the server out of the equipment rack.

Note –

When drawing out the M4000/M5000 server to the front, release the cable tie

holding the PCI cables on the rear of the server.

4. Remove the top cover.

This step includes deploying the rack’s antitilt features (if applicable), sliding the
server out of the equipment rack, and removing the top cover. See

Section 5.2.1,

“Removing the Top Cover” on page 5-5

.

Caution –

The motherboard unit is a long and heavy assembly that houses the

system motherboard on the underside. Two people are recommended to lift the unit.