Chapter 13

Motherboard Unit Replacement 13-17

13.2.5

Accessing the M5000 Server DC-DC Converter

Caution –

There is an electrical hazard if the power cords are not disconnected. All

power cords must be disconnected to completely remove power from the server.

1. Power off the server.

This step includes turning the key switch to the Service position, confirming that
the POWER LED is off, and disconnecting power cables. See

Section 4.4.1,

“Powering the Server Off Using Software” on page 4-12

.

Caution –

To prevent the equipment rack from tipping over, you must deploy the

antitilt feature, if applicable, before you slide the server out of the equipment rack.

Note –

When drawing out the M4000/M5000 Server to the front, release the cable tie

holding the PCI cables on the rear of the server.

2. Remove the top cover.

This step includes deploying the rack’s antitilt features (if applicable), sliding the
server out of the equipment rack, and removing the top cover. See

Section 5.2.1,

“Removing the Top Cover” on page 5-5

.

Caution –

Use proper ESD grounding techniques when handling components. See

Section 1.1, “Safety Precautions” on page 1-1

.

3. Remove the memory boards adjacent to the DC-DC converter being replaced.

See

Section 11.1.2, “Removing the Memory Board” on page 11-5

.