2 accessing the operator panel, 1 removing the operator panel, Accessing the operator panel – FUJITSU M5000 User Manual

Page 252: Removing the operator panel

Advertising
background image

15-4

SPARC Enterprise M4000/M5000 Servers Service Manual • December 2010

15.2

Accessing the Operator Panel

Caution –

There is an electrical hazard if the power cords are not disconnected. All

power cords must be disconnected to completely remove power from the server.

Caution –

Use proper ESD grounding techniques when handling components. See

Section 1.1, “Safety Precautions” on page 1-1

.

1. Power off the server.

This step includes turning the key switch to the Service position, confirming that
the POWER LED is off, and disconnecting power cables. See

Section 4.4.1,

“Powering the Server Off Using Software” on page 4-12

.

Caution –

To prevent the equipment rack from tipping over, you must deploy the

antitilt feature, if applicable, before you slide the server out of the equipment rack.

Note –

When drawing out the M4000/M5000 server to the front, release the cable tie

holding the PCI cables on the rear of the server.

2. Deploy the rack’s antitilt features (if applicable) and slide the server out of the

equipment rack.

See

Section 5.1.1, “Sliding the Server Out of the Equipment Rack” on page 5-2

.

3. Remove the 172-mm fan units.

See

Section 10.1.6, “Removing the 172-mm Fan Module” on page 10-8

.

4. Loosen the three (3) captive screws and remove the fan cage.

The M4000 server uses only two (2) captive screws.

15.2.1

Removing the Operator Panel

Caution –

Use proper ESD grounding techniques when handling components. See

Section 1.1, “Safety Precautions” on page 1-1

.