Page 22: Checking the installation location

Advertising
background image

2-8

SPARC Enterprise M4000/M5000 Servers Installation Guide • December 2010

2.2.2

Cable Connections

TABLE 2-3

lists the powercords for the servers.

Note –

For servers that have the B-type plug, confirm that a 20A overcurrent

protection device is available outside the server. If one is not available, prepare an
external 20A overcurrent protection that can be achieved by means of no-fuse
breakers (NFBs) or fuses. The B-type plug refers to plugs other than grounding-type
ones with two parallel blades, such as the NEMA L6-30, L6-20, L6-15, and L5-15.

Refer to the SPARC Enterprise M4000/M5000 Servers Site Planning Guide for electronic
specifications of the midrange servers.

2.2.3

Checking the Installation Location

When installing the server, consider not only the device sizes but also the sizes of the
required service areas (maintenance areas). For details, refer to the SPARC Enterprise
M4000/M5000 Servers Site Planning Guide
and the manual that came with the rack.

The site electrician should verify the proper electrical hookups.

TABLE 2-3

Power Cords

System

Location

Powercord type

SPARC Enterprise
M4000

Server

Connector

Americas, Taiwan
Korea, Japan

NEMA L5-15 125V 15A
NEMA L6-20 250V 20A

Rest of the world

IEC60309 16A 250V, 3PIN with IEC 60320

C20

SPARC Enterprise
M5000

Server

Connector

Americas, Taiwan
Korea, Japan

NEMA L5-15 125V 15A
NEMA L6-20 250V 20A

Rest of the world

IEC60309 16A 250V, 3PIN with IEC 60320

C20