A pcu fan has failed, Telnet to the affected sun storedge t3+ array, Run refresh -s to verify the battery state – Sun Microsystems StorEdge 6900 Series User Manual

Page 127: Replace the battery, if necessary, Telnet to affected sun storedge t3+ array, Verify the fan state with fru stat, Replace the power cooling unit, if necessary, For internal use only

Advertising
background image

Chapter 8

Troubleshooting the Sun StorEdge T3+ Array Devices

111

For Internal Use Only

t3

power.
battery

Alarm-

Red

Y

[ Info/Action ] The
state of
power.u1pcu1.BatStat
e on diag213
(ip=xxx.20.67.213) is
Fault

Possible causes are:
1. Voltage level on

power supply and
battery have
moved out of
acceptable
thresholds.

2. The internal PCU

temp has exceeded
acceptable
thresholds.

3. A PCU fan has

failed.

Information: The state
of the batteries in the
Sun StorEdge T3+
array is not optimal.

Recommended action:

1. Telnet to the

affected Sun
StorEdge T3+
array.

2. Run

refresh -s

to verify the
battery state.

3. Replace the

battery, if
necessary

t3

power.fan

Alarm-

Red

Y

[ Info/Action ] The
state of
power.u1pcu1.Fan1Sta
te on diag213
(ip=xxx.20.67.213) is
Fault

Information: The state
of a fan on the Sun
StorEdge T3+ array is
not optimal.

Recommended action:

1. Telnet to affected

Sun StorEdge T3+
array.

2. Verify the fan state

with

fru stat.

3. Replace the power

cooling unit, if
necessary.

Category

Component

EventType

Sev

Action

Description

Information