Plan, Marley, Sigma 1200 – SPX Cooling Technologies 1000 User Manual

Page 11: Cooling tower, Engineering data : concrete basin

Advertising
background image

Marley

/

Sigma 1200

Cooling Tower

/

Engineering Data : Concrete Basin

11

NotE

1 Use this bulletin for preliminary layouts only. Do not use for

construction. Obtain current drawings from your Marley sales

representative. Concrete basin design and construction are by

other contractors or purchaser.

2 Operating weight is total wet operating weight of tower only,

excluding water in concrete basin.

3 Maintain at least 2'-0" of clear space at endwall faces

for construction purposes. Air inlet faces must have

an unobstructed air supply. Consult your Marley sales

representative for recommendations if nearby obstructions may

interfere.

4 Minimum basin depth is 1'-6". Maximum basin depth is

5'-6". Extended interior columns for deep basins are available as

an option. Perimeter columns remain at 1'-6" below top of basin

curb.

5 All anchor bolts complete with nut and washer must be

furnished by others. Bolts must be

3

4

" diameter with 2" all-

thread projection.

6 Other contractors or purchaser must design, construct, and

furnish sump and overflow to suit requirements.

Tower

Model

Dimensions

Operating Weight lb

W

A

B

Single Cell

Each Cell Add

1211

31'-6

3

4

"

4

16'-0"

39040

35910

1221

33'-6

3

4

"

4

16'-0"

41960

39420

1231

33'-6

3

4

"

5

20'-0"

49100

46560

1241

33'-6

3

4

"

6

24'-0"

59020

56470

1251

37'-6

3

4

"

6

24'-0"

61200

58530

1261

37'-6

3

4

"

7

28'-0"

70900

68240

1’-6

1'-0 RECOMMENDED
OPERATING WATER LEVEL

1’-6

1'-0 RECOMMENDED
OPERATING WATER LEVEL

FLAt BAsiN sEctioN

dEEP BAsiN sEctioN

A

BAYS @ 4'-0" =

B

PER CELL

6"

AIR INLET FACE

CL

COL.

CL COL.

6" MIN.

6" MIN.

6"

W

IN

TO IN OF BASIN W

ALLS

AIR INLET FACE

ENDW

ALL

F

ACE

ENDW

ALL

F

ACE

6" MIN.

6" MIN.

PLAN