Marley

/

Sigma 1000

Cooling Tower

/

Engineering Data : Support

6

W

OVERALL

WIDTH OF BASIN

C

BAYS @ 4'-0 =

L

EACH ADDITIONAL CELL =

L

7

1/2

"

7

1/2

"

AIR INLET FACE

11

1/2

"

A

C L

C L

OVERALL LENGTH OF BASIN

CL

CL

B

A

B

C L

TOWER

C L

C L

AIR INLET FACE

ENDW

ALL

F

ACE

ENDW

ALL

F

ACE

OVERFLOW

SUMP

ADDITIONAL SUMP

WHEN REQUIRED

11

1/2

"

7/8"

ANCHOR

BOL

T HOLES

7/8"

ANCHOR

BOL

T HOLES

7/8" ANCHOR

BOLT HOLES

CL

7/8" ANCHOR

BOLT HOLES

7/8" ANCHOR

BOLT HOLES

PLAN

NotE

1 Use this bulletin for preliminary layouts only. All

dimensions show anchor bolt locations. Obtain current

drawings from your Marley sales representative before

designing supports.

2 Other contractors or purchaser must design and erect

supporting steel.

3 If steel beams are used, they must include

7

8

" dia. holes to

accept anchor bolts provided. If concrete beams or pilasters

are used,

3

4

" dia. anchor bolts embedded in the concrete must

be provided by others.

4 Maintain no less than 2'-0" of clear space at endwall faces for

construction purposes. Air inlet faces must have unobstructed

air supply. Consult your Marley sales representative if nearby

obstructions may interfere.

5 Operating weight is wet weight of tower and wood basin,

including 6" of water in the collection basin. This is the

recommended operating water level for all models.

Tower

Model

Dimensions

Operating Weight lb

W

A

B

C

L

Single Cell

Each Cell Add

1011

22'-1"

4'-10"

5'-3"

2

8'-0"

23620

20500

1021

22'-1"

4'-10"

5'-3"

3

12'-0"

32140

28980

1031

24'-5"

4'-10"

6'-5"

3

12'-0"

34440

31020

1041

26'-8"

4'-10"

7'-6

1

2

"

4

16'-0"

47620

44000