Marley, Specifications: options – SPX Cooling Technologies 1000 User Manual

Page 28

Advertising
background image

Specifications

Marley

/

Sigma 1000/1200

Cooling Tower

/

Specifications: Options

28

Specification Value

Low Noise Tower:

1.1

Add the following at the end of this

paragraph: The cooling tower shall be

quiet operating, and shall produce an

overall level of sound no higher than ____

dBA at the critical location indicated on

the Plans.

Sound produced by a Sigma Steel tower operating in an unob-

structed environment will meet all but the most restrictive noise

limitations – and will react favorably to natural attenuation.

Where the tower has been sized to operate within an enclosure,

the enclosure itself will have a damping effect on sound. Sound

also declines with distance – by about 5 or 6 dBA each time

the distance doubles. Where noise at a critical point is likely to

exceed an acceptable limit, you have several options – listed

below in ascending order of cost impact:

• Where only a slight reduction in noise will satisfy — and the

source of concern is in a particular direction — merely turning

the tower may be the answer. Less sound emanates from the

cased face of the tower than does from the air intake face.

• In many cases, noise concerns are limited to nighttime, when

ambient noise levels are lower and neighbors are trying to

sleep. You can usually resolve these situations by using two-

speed motors in either 1800/900 or 1800/1200 RPM configura-

tion; and operating the fans at reduced speed without cycling

“after hours”. (The natural nighttime reduction in wet-bulb tem-

perature makes this a very feasible solution in most areas of the

world, but the need to avoid cycling may cause the cold water

temperature to vary significantly.)

• Variable speed drives automatically minimize the tower's noise

level during periods of reduced load and/or reduced ambient

without sacrificing the system's ability to maintain a constant

cold water temperature. This is a relatively inexpensive solution,

and can pay for itself quickly in reduced energy costs.

• Where noise is a concern at all times (for example, near a hos-

pital), the best solution is to oversize the tower so it can operate

continuously at reduced (1200 or 900 RPM) motor speed even at

the highest design wet-bulb temperature. Typical sound reduc-

tions are 7 dBA at 2/3 fan speed or 10 dBA at 1/2 fan speed, but

larger reductions are often possible.

• Extreme cases may require inlet and discharge sound attenu-

ator sections; however, the static pressure loss imposed by

attenuators may necessitate an increase in tower size. This is

the least desirable approach because of the significant cost

impact – and because of the obstruction to normal maintenance

procedures.

Your Marley representative can help you meet your sound

requirements.

Advertising
This manual is related to the following products: