Marley, Sigma 1000, Cooling tower – SPX Cooling Technologies 1000 User Manual

Page 7: Engineering data : concrete basin

Advertising
background image

Marley

/

Sigma 1000

Cooling Tower

/

Engineering Data : Concrete Basin

7

NotE

1 Use this bulletin for preliminary layouts only. Do not use for

construction. Obtain current drawings from your Marley sales

representative. Concrete basin design and construction are by

other contractors or purchaser.

2 Operating weight is total wet operating weight of tower only,

excluding water in concrete basin.

3 Maintain at least 2'-0" of clear space at endwall faces for

construction purposes. Air inlet faces must have unobstructed

air supply. Consult your Marley sales representative for

recommendations if nearby obstructions may interfere.

4 Minimum basin depth is 1'-6". Maximum basin depth is 5'-6".

Extended interior columns for deep basins are available as an

option. Perimeter columns remain at 1'-6" below top of basin

curb.

5 All anchor bolts complete with nut and washer must be

furnished by others. Bolts must be

3

4

"diameter with 2" all-thread

projection.

6 Other contractors or purchaser must design, construct, and

furnish sump and overflow to suit requirements.

Tower

Model

Dimensions

Operating Weigt lb

W

A

B

Single Cell

Each Cell Add

1011

21'-10"

2

8'-0"

15120

13500

1021

21'-10"

3

12'-0"

20160

18400

1031

24'-2"

3

12'-0"

21240

19500

1041

26'-5"

4

16'-0"

29020

27200

1’-6

1'-0 RECOMMENDED
OPERATING WATER LEVEL

1’-6

1'-0 RECOMMENDED
OPERATING WATER LEVEL

A

BAYS @ 4'-0" =

B

PER CELL

6"

AIR INLET FACE

CL

COL.

CL COL.

6" MIN.

6" MIN.

6"

W

IN

TO IN OF BASIN W

ALLS

AIR INLET FACE

ENDW

ALL

F

ACE

ENDW

ALL

F

ACE

6" MIN.

6" MIN.

FLAt BAsiN sEctioN

dEEP BAsiN sEctioN

PLAN