Specifications

Marley

/

Sigma 1000/1200

Cooling Tower

/

Specifications: Options

24

Specification Value

to modulate fan speed maintaining set

point temperature. The drive's panel dis-

play shall be able to display the set-point

temperature and cold-fluid temperature

on two separate lines. The bypass shall

include a complete magnetic bypass

circuit and with capability to isolate the

VFD when in the bypass mode. Transfer

to the bypass mode shall be manual in

the event of VFD failure. Once the motor

is transferred to the by-pass circuit the

fan motor will run at constant full speed.

The bypass circuit will not modulate ON

and OFF based on fluid temperature. The

application must be able to handle very

cold fluid temperatures while the VFD

is in a by-pass mode. Operator controls

shall be mounted on the front of the

enclosure and shall consist of start and

stop control, bypass/VFD selection, Auto/

Manual selections, manual speed control.

To prevent heating problems in the fluid

cooloer fan motor and to assure proper

gear reducer lubrication the VFD system

shall de energize the motor once 25%

motor speed is reached and cooling is no

longer required. The fluid cooler manu-

facturer shall supply VFD start-up assis-

tance. Tower vibration testing throughout

the speed range is required to identify

and lockout any natural frequency vibra-

tion levels which may exceed CTI guide-

lines.

Marley Premium VFD System

6.4 Add the following paragraph in the

Mechanical Equipment section when

VFD is used as a stand alone system:

A complete UL listed Variable Speed

Drive system in a NEMA 12 indoor

or NEMA 3R outdoor enclosure shall

be provided. The VFD shall use PWM

technology with IGBT switching and

integrated bypass design. VFD output

switching shall not cause mechanical

issues with gearbox teeth or drive shafts.

The VFD shall catch a fan spinning in the

reverse direction without tripping. The

panel shall include a main disconnect

with short circuit protection and external

operating handle, lockable in the off posi-

tion for safety. The system shall include

a solid state, PI temperature controller

to adjust frequency output of the drive

in response to the tower fluid tempera-

ture. The temperature of the fluid and

Advertising