Plan endwall elevation, Marley, Sigma 1000 cooling tower – SPX Cooling Technologies 1000 User Manual

Page 4: Engineering data : schematic

Advertising
background image

Marley

/

Sigma 1000

Cooling Tower

/

Engineering Data : Schematic

4

B

H

TOP OF
FAN CYLINDER

BASE OF
TOWER COLUMNS

TOP OF
FAN DECK

W

OUT

T

O OUT

OF

TOWER

5"

CL

COL.

A

BAYS @ 4'-0 =

L

CL

COL.

CL

COL.

5"

C

DIA. FAN

PLAN

ENdwALL

ELEvAtioN

NotE

1 Last number of model indicates number of cells. Change as

appropriate for your selection. Primary engineering data is per

cell.

2 Fan hp is usually less than shown here.

3 Height shown is from base of tower columns to fan deck.

Wood basin, if used, elevates tower 6

1

4

". If concrete basin is

used, subtract 1'-6" for height above top of basin curb.

Tower

Model

GPM

per cell

Width

W

Length

L

Height

H

A

B

C

Maximum

Motor hp

Static

Lift

1011

380 - 2140

21'-5"

8'-0"

11'-8

5

8

"

2

3'-8"

84"

30

11.7'

1021

580 - 3220

21'-5"

12'-0"

11'-8

5

8

"

3

3'-5"

96"

30

11.7'

1031

580 - 3220

23'-9"

12'-0"

11'-8

5

8

"

3

3'-8"

120"

50

11.7'

1041

790 - 4300

26'-0"

16'-0"

11'-8

5

8

"

4

4'-0"

144"

60

11.7'

Advertising
This manual is related to the following products: