Plan endwall elevation, Marley, Sigma 1200 – SPX Cooling Technologies 1000 User Manual

Page 9: Cooling tower, Engineering data : piping

Advertising
background image

Marley

/

Sigma 1200

Cooling Tower

/

Engineering Data : Piping

9

NotE

1 Use this bulletin for preliminary layouts only. Obtain current

drawings from your Marley sales representative.

2 Pumping head contributed by the tower is static lift shown

on page 9. Actual pumping head will vary according to tower

circulating GPM. Total pumping head will be furnished at time

of proposal.

3 If your application requires a bypass system, recommended

location is through tower endwall into plenum area. Review

of the system by SPX Cooling Technologies engineering is

required.

4 Marley piping terminates at face of a cast iron flat face flange

which conforms to class 125 lb. ASME B 16.1 specifications.

5 Supports on tower for crossover piping are are part of the tower

design. Do not support the riser’s dead load or operating load

from the tower. Do not brace the riser’s seismic or thrust loads

against the tower.

Tower

Model

GPM

Per Cell

Dimensions

A

B

C

D

E

F

G

1211

1050 - 5750

16"

12"

8'-0"

16'-0"

13'-2

3

4

"

16'-6

3

8

"

15'-6

3

8

"

1221

1050 - 5750

16"

12"

8'-0"

16'-0"

14'-2

3

4

"

17'-6

3

8

"

15'-6

3

8

"

1231

1320 - 7200

16"

12"

10'-0"

20'-0"

14'-2

3

4

"

17'-6

3

8

"

15'-6

3

8

"

1241

1500 - 7050

16"

12"

12'-0"

24'-0"

14'-2

3

4

"

17'-6

3

8

"

15'-6

3

8

"

1241

7051 - 8650

20"

16"

12'-0"

24'-0"

14'-5

3

4

"

17'-6

3

8

"

15'-8

3

8

"

1251

1500 - 7050

16"

12"

12'-0"

24'-0"

16'-2

3

4

"

19'-6

3

8

"

15'-6

3

8

"

1251

7051 - 8650

20"

16"

12'-0"

24'-0"

16'-5

3

4

"

19'-6

3

8

"

15'-8

3

8

"

1261

1850 - 7050

16"

12"

14'-0"

28'-0"

16'-2

3

4

"

19'-6

3

8

"

15'-6

3

8

"

1261

7051 - 10100

20"

16"

14'-0"

28'-0"

16'-5

3

4

"

19'-6

3

8

"

15'-8

3

8

"

G

BASE OF

TOWER COLUMNS

C L

INLET

F

MINIMUM

CL

INLET

CL

COL.

C

CL

INLET

D

TYP. MULTI-CELL

PIPING SHOWN WITH

DASHED LINES IS BY OTHERS

E

FACE OF

A

DIA.

INLET PIPING

C L

TOWER

FAN

C L

TOWER

FAN

B

DIA. FLOW CONTROL

VALVE AND CROSS OVER

PIPING

PLAN

ENdwALL

ELEvAtioN

Advertising
This manual is related to the following products: