Specifications

Marley

/

Sigma 1000/1200

Cooling Tower

/

Specifications: Options

23

Specification Value

Basin Heater:

10.2 Add the following paragraph in the

Cold Water Basin section: Provide

a system of electric immersion heat-

ers and controls for each cell of the

tower to prevent freezing of water in

the collection basin during periods of

shutdown. The system shall consist

of one or more stainless steel elec-

tric immersion heaters installed in a

galvanized steel heat shield provided

in the floor of the basin. A NEMA

4 enclosure shall house a magnetic

contactor to energize heaters; a trans-

former to provide 24 volt control circuit

power; and a solid state circuit board

for temperature and low water cutoff.

A control probe shall be located in the

basin to monitor water level and tem-

perature. The system shall be capable

of maintaining 40°F water temperature

at an ambient air temperature of __ °F.

Wiring of the heaters and controls shall

be the responsibility of the purchaser.

Fan Motor Variable Speed Drive:

Marley All Weather ACH550 System

6.4 Add the following paragraph in the

Mechanical Equipment section when

VFD is used with customers Building

Management System: A complete

UL listed Variable Speed Drive system

in a NEMA 1 indoor, NEMA 12 indoor

or NEMA 3R outdoor enclosure shall

be provided. The VFD shall use PWM

technology with IGBT switching and

integrated bypass design. VFD out put

switching shall not cause mechanical

issues with gearbox teeth or drive shafts.

The VFD shall catch a fan spinning in

the reverse direction without tripping.

The panel shall include a main discon-

nect with short circuit protection and

external operating handle, lockable in the

off position for safety. The VFD system

shall receive a speed reference signal

from the Building Management System

monitoring the tower fluid temperature.

As an option to receiving the speed

reference signal from a building manage-

ment system, the drive must have the

capability to receive a 4-20 ma tempera-

ture signal from an RTD transmitter. The

VFD shall have an internal PI regulator

The basin heater components described at left represent our rec-

ommendation for a reliable automatic system for the prevention

of basin freezing. They are shipped separately for installation at

the jobsite.

If aggressive operating conditions are anticipated, change “galva-

nized” in paragraph 10.2 to “Series 300 SS”.

The ambient air temperature that you fill in should be the lowest

1% level of winter temperature prevalent at site.

Ask for Marley drawing 92-3627.

Marley VFD drive systems are designed to combine absolute

temperature control with ideal energy management. The cool-

ing tower user selects a cold water temperature and the drive

system will vary the fan speed to maintain that temperature.

Precise temperature control is accomplished with far less stress

to the mechanical equipment components. The improved energy

management provides fast payback. Indeed, many utilities offer

generous rebates for users having installed VFD drives.