Specifications: Options

26

Specification Value

Convenience and Safety Options

Stairway:

9.3 Replace paragraph 9.3 with the fol-

lowing: A 30" wide, column supported,

45° stairway with 8" rise and run of

treated Douglas Fir shall be provided

at the tower endwall rising from grade

(roof) to the fan deck elevation. Stair

columns shall be 4x4. Guardrails shall

be 2"x4". The upper guardrail shall have

an eased edge for the protection of

operating personnel. Stairway founda-

tion shall be by others, designed in

accordance with drawings provided by

the cooling tower manufacturer. The

stairway shall conform to OSHA stan-

dards.

Plenum Walkway:

9.1

Add the following to the end of this

paragraph: Provide a 30" wide walkway

extending from one endwall access door

to the other through the length of the

tower. Walkway shall be constructed of

treated Douglas Fir, and the top of the

walkway shall be above the cold water

basin overflow level. If the cold water

basin is deeper than 4'-0", the walkway

shall be equipped with guardrails.

Ladder Extension:

9.4

Add the following paragraph in the

Access and Safety section: Provide

a ladder extension for connection to

the base of the ladder attached to

the tower casing. This extension shall

be long enough to rise from the roof

(grade) level to the base of the tower.

Anchorage and lateral bracing of the

ladder extension shall be by others.

Ladder Safety Cage:

9.3 Add the following to the end of this

paragraph: A heavy gauge galvanized

steel safety cage shall surround the

ladder, extending from a point approxi-

mately 7'-0" above the base of the

ladder to the top of the guardrail sur-

rounding the fan deck.

Although they are not neces-

sary for routine operation and

maintenance, stairways do

provide a safe and comfort-

able means of access to the

top of the tower that is often

overlooked in the initial cool-

ing tower purchase. They are

designed in straight-run or

double-back configurations

to accommodate your site

requirements.

This option permits freedom of movement for inspection or main-

tenance within the tower without the need for wading boots or

tower drainage. It also helps prevent maintenance personnel from

damaging submerged accessories in the cold water basin (such

as screens, probes, basin heaters, etc.).

Many towers are installed such that the base of the tower is 2’-0”

or more above the roof or grade level. This makes it difficult to

get up to the base of the attached ladder. The ladder extension

alleviates this problem. Marley ladder extensions are available in

standard 5’-0” and 11’-0” lengths, and will be field-cut to fit.

To meet OSHA guidelines, towers whose

fan decks are 20'-0" or more above roof or

grade, and which are equipped with lad-

ders, are required to have safety cages sur-

rounding the ladders.