Marley, Cooling tower, Specifications: base – SPX Cooling Technologies 1000 User Manual

Page 21

Advertising
background image

Specifications

Specification Value

Marley

/

Sigma 1000/1200

Cooling Tower

/

Specifications: Base

21

9.3

Each endwall of the tower shall be

equipped with a 20" wide aluminum

vertical ladder, through-bolted to the

endwall structure. Ladder shall rise

from the cold water basin level to the

top of the fan deck guardrail, and shall

be designed and installed in confor-

mance with OSHA standards.

10.0 Cold Water Collection Basin:

10.1 The cold water collection basin shall be

of poured-in-place concrete, provided

under scope of work done by others.

The concrete basin design shall be

based upon certified loads and dimen-

sions provided by the cooling tower

manufacturer.

11.0 Scope of Work:

11.1 The cooling tower manufacturer shall

be responsible for the design, fabrica-

tion, and delivery of materials to the

project site, and for the erection of

the tower over supports provided by

others. Unless otherwise specified, all

external piping, pumps, controls, and

electrical wiring will be outside the

cooling tower manufacturer's scope of

work.

For the comfort and safety of your operat-

ing personnel, the Sigma tower includes a

ladder and guardrail of the quality and

design indicated—and we strongly

recommend that you require it of all

bidders! Portable ladders and other

“make-do” access means are inappro-

priate for equipment of this size and

complexity.

This basic specification assumes that the tower will be erected

over a concrete basin at grade level. If the tower is to be installed

on an elevated supporting platform, the plywood cold water

collection basin indicated on page 17 should be included in the

specifications.

Please be clear in your specifications

and inquiry documents regarding

the full scope of work expected.

That will help assure that your bid

comparisons will be made on as

equal a basis as possible—and

will help to avoid any misunder-

standings during the execution

and implementation of the

contract.

Advertising
This manual is related to the following products: