Specifications: Options

25

Specification Value

set point shall be displayed on the door

of the control panel. The bypass shall

include a complete magnetic bypass

circuit with capability to isolate the VFD

when in the bypass mode. Transfer to

the bypass mode shall be automatic in

the event of VFD failure or for specific

trip conditions allowing safe transfer of

utility voltage to the motor. Automatic

bypass with an earth ground condition

is not allowed. The bypass contactor

shall be cycled on and off while operat-

ing in bypass, to maintain the set-point

temperature of the cold water. The drive

design shall be operated as a stand-alone

system without the need for a BMS sys-

tem. Operator controls shall be mounted

on the front of the enclosure and shall

consist of start and stop control, bypass/

VFD selector switch, Auto/Manual selec-

tor switch, manual speed control, and

solid-state temperature controller. An

emergency bypass selector switch inter-

nal to the panel allowing the fluid cooler

fan motor to be run at full speed shall be

furnished. To prevent heating problems in

the fluid cooler fan motor and to assure

proper gear box lubrication the VFD sys-

tem shall de energize the motor once

25% motor speed is reached and cool-

ing is no longer required. The VFD shall

include de-icing logic with auto canceling

and adjustable time. Speed in De-Ice

mode shall not exceed 50% motor

speed. The fluid cooler manufacturer

shall supply VFD start-up assistance.

Tower vibration testing throughout the

speed range is required to identify and

lockout any natural frequency vibration

levels which may exceed CTI guidelines.

Vibration Limit Switch:

5.8 Add the following paragraph in the

Mechanical Equipment section: A

single-pole, double-throw vibration limit

switch in a NEMA 4 housing shall be

installed on the mechanical equipment

support for wiring into the owner’s

control panel. The purpose of this

switch will be to interrupt power to the

motor in the event of excessive vibra-

tion. It shall be adjustable for sensitiv-

ity, and shall require manual reset.

Unless specified otherwise, a Metrix

switch will be provided. A double-pole,

double-throw model is also available. If

purchased in conjunction with the Control

System, it is also factory-wired. The

requirement for manual reset assures that

the tower will be visited to determine the

cause of excess vibration.