Specifications

Specification Value

Marley

/

Sigma 1000/1200

Cooling Tower

/

Specifications: Base

17

4.0

Fan Deck and Fan Cylinder:

4.1

The fan deck shall act as a working

platform for maintenance personnel.

It shall be fabricated of no less than

1" thick, 7 ply, exterior grade, treated

Douglas Fir plywood, and shall be

designed for a uniform live load of

60 psf or a concentrated load of 600

pounds.

4.2

Fan cylinders shall be molded FRP.

They shall be anchored to the fan deck

structure to provide a consistently

stable operating shroud for the fan.

Fan cylinders less than 72" in height

shall be equipped with a heavy gauge,

removable, hot-dip galvanized steel fan

guard for the protection of operating

personnel.

The indicated design values for framing and decking not only give

you assurance that the tower can withstand long term operation

in a hostile environment—but that it will accept many years of

inspection and maintenance traffic by your operating personnel.

Fiberglass-reinforced polyester fan cylinders provide the close tip

clearances and smooth airflow contour necessary for good fan

performance. The inert, noncorroding nature of FRP assures that

these characteristics will persist.

Even in aggressive water conditions, the heavy construction of

the fan guard normally precludes the need for stainless steel.