Specifications

Marley

/

Sigma 1000/1200

Cooling Tower

/

Specifications: Options

29

Specification Value

Watertight Partitions Between Cells:

3.5 Replace the last sentence in this

paragraph with the following:

Partitions shall be 3/4" x 5-ply, factory-

fabricated, grooved and splined treated

Douglas Fir plywood sheets, installed

and sealed watertight to permit inde-

pendent cell operation.

Fire Safety Options:

In addition to the normal partition function of preventing air

bypass (page 17), this option allows you to use each partitioned

cell of your tower independently. This is valuable where a single

multicell tower is serving several separate systems—or where

winter operation may require less than full tower capability.

Occasionally, critical processes or local codes may require you to

install a fire-protection sprinkler system on a wood tower—or pay

higher insurance premiums—or both. Our first recommendation

in such a case would be for you to consider using a Sigma Steel

cooling tower, as listed in the Factory Mutual Approval Guide.

Another alternative that could be acceptable to your insurance

carrier, and which you may wish to evaluate, would be to make

your Sigma tower as fire resistant as possible. This can be done

by any or all of the following measures:

• FRP casing having a flame spread rating of 25 or less. (Para. 8.1)

• Fan cylinders of fire-retardant FRP having a flame spread rating

of 25 or less. (Para. 4.2)

1

4

" thick fireproof fiber reinforced cement overlay over the fan

deck—and will provide FRC overlaid distribution basin covers.

(Para. 4.1)

3

4

" thick plywood partitions both sides of the column line

between cells to achieve a fire rating of at least 30 minutes.

(Para. 3.5 and this page.)