Chapter 3 Operation

Series 24-HP Instruction Manual

3-10

IM-24-HP

Energy Menu – For EMS Energy Meters Only



Configuration:

There are several possibilities regarding the measurement of water or steam energy given the location
of the meter and the use of a second RTD. The table below summarizes the possibilities:

Fluid

Meter Location

Second RTD

Measurement

Water

“Sent” Flow Line

“Return Flow Line

Change in Energy

Water

“Return” Flow Line “Sent” Flow Line

Change in Energy

Water

“Sent” Flow Line

None

Outgoing Energy

Steam

“Sent” Flow Line

“Return” Flow Line
(condensate)

Change in Energy

Steam

“Sent” Flow Line

None

Outgoing Energy



As above, you must properly configure the meter in the Energy Menu.
1. Loc in Sent Flow? Select Yes or No based on where the meter is located. Refer to the above

table

2. Heating System? Select Yes for a hot water system used for heating. Select No for a chilled

water system used for cooling. Always select Yes for a steam system.

3. % Returned. Select a number between 0% and 100%. Estimate the amount of water that returns.

It is usually 100%, or can be less than 100% if historical data shows the amount of makeup water
used. If a second RTD is not used, set to 0%. When 0% is selected, the energy calculation
represents the outgoing energy only (no return energy is subtracted). NOTE: the meter ships
from the factory assuming 0% return and has a 1000 ohm resistor installed in the RTD #2
wiring location. This needs to be removed if the meter is to be used in a manner other than
with 0% return and with the customer supplied RTD in its place.