Series 24-HP Instruction Manual

Appendix E MODBUS Commands

IM-24-HP

E-7

The start address is equal to the desired first register number minus one. The

addresses derived from the start address and the number of registers must all be

mapped to valid defined registers, or an invalid data address exception will oc-

cur.

Normal Response Message Format

Exception Response Message Format

Examples

Read the exception status byte from the device with address 1:

01 07 41 E2

01 Device address
07 Function code, 04 = read exception status

A typical response from the device is as follows:

01 07 03 62 31

01 Device address
07 Function code
03 Exception status byte
62 31 CRC

Request the first 12 registers from device with address 1:

01 04 00 00 00 0C F0 0F

01 Device address
04 Function code, 04 = read input register
00 00 Starting address
00 0C Number of registers = 12
F0 0F CRC





A typical response from the device is as follows: *note these are the older regis-