Lennox Hearth ADAGIO-MP User Manual

Page 17

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

17

Remember to maintain 1" (25 mm) clearance

to combustibles, framing members, and attic

or ceiling insulation when running vertical

chimney sections.

G. Support the vertical run sections -

On the vertical run, support the venting sys-

tem every 8 feet (2.4m) above the fireplace

vent outlet with field provided support straps

(Plumber's tape). Attach the straps to the vent

pipe and secure to the framing members with

nails or screws.

H. Change vent direction - At transition from or

to a horizontal/inclined run, install the SV4.5E45

and SV4.5E90 elbows in the same manner as

the straight vent sections. The elbows feature a

twist section to allow them to be routed about the

center axis of their initial collar section to align

with the required direction of the next vent run

element.

Twist elbow sections in a clockwise

direction only so as to avoid the possibility of

unlocking any of the previously connected vent

sections. See Figure 16 on Page 14.

I. Continue installation of horizontal/inclined

sections - Continue with the installation of the

straight vent sections in horizontal/inclined run

as described in Step E. Install support straps

every 5 ft. (1.52 m) along horizontal/inclined

vent runs using conventional plumber’s tape.

See Figure 26, it is very important that the

horizontal/inclined run be maintained in a

straight (no dips) and recommended to be in

a slightly elevated plane, in a direction away

from the fireplace of 1/4" rise per foot (20 mm

per meter) which is ideal, though rise per foot

run ratios that are smaller are acceptable all the

way down to at or near level. Use a carpenter’s

level to measure from a constant surface and

adjust the support straps as necessary.

HORIZONTAL (OUTSIDE WALL) TERMINATION

SYSTEM

Figures 26, and Figures 29 to 32 on Pages

17, 19 and 20 and their associated Horizontal

Vent Table illustrate the various horizontal

venting configurations that are possible for

use with these appliances.

Secure Vent™ pipe

applications are shown in these figures;

Secure

Flex™ pipe may also be used. A Horizontal Vent

Table summarizes each system’s minimum and

maximum vertical and horizontal length values

that can be used to design and install the vent

components in a variety of applications.

Both of these horizontal vent systems terminate

through an outside wall. Building Codes limit or

prohibit terminating in specific areas. Refer to

Figure 5 on Page 7 for location guidelines.

Secure Vent SV4.5 direct vent system compo-

nents are unitized concentric pipe components

featuring positive twist lock connection, (refer

to Figures 15 and 16 on Page 14). All of the

appliances covered in this document are fitted

with collars having locking inclined channels.

The dimpled end of the vent components fit

over the appliance collar to create the positive

twist lock connection.

A. Plan the vent run -

Analyze the vent routing and determine the

types and quantities of sections required

4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2"

(572 mm), 34-1/2" (876 mm) and 46-1/2" (1181

mm) net section lengths are available. Plan the

vent lengths so that a joint does not occur at

the intersection of ceiling or roof joists. Make

allowances for elbows as indicated in

Figure

18 on Page 14.

Maintain a minimum 1" (25 mm) clearance to

combustibles on the vertical sections. Clear-

ances for the horizontal runs are; " (76 mm)

on top, 1" (25 mm) on sides, and 1" (25 mm)

at the bottom.

B. Frame exterior wall opening -

Locate the center of the vent outlet on

the exterior wall according to the dimen-

sions shown in

Figure 9 on Page 9. Cut

and/or frame an opening, 10-1/2" x 12-1/8"

(267 mm x 308 mm) inside dimensions, about

this center.

C. Frame ceiling opening - If the vertical route

is to penetrate a ceiling, use plumb line to locate

the center above the appliance. Cut and/or frame

an opening, 10-1/2" x 10-1/2" (267 mm x 267

mm) inside dimensions, about this center (refer

to

Figure 14 on Page 13).

D. Attach vent components to appliance - To

attach a vent component to the appliance collar,

align the dimpled end over the collar, adjust-

ing the radial alignment until the four locking

dimples are aligned with the inlets of the four

incline channels on the collar (refer to Figure

15 on Page 14).

Push the vent component against the collar

until it fully engages, then twist the component

clockwise, running the dimples down and along

the incline channels until they seat at the end

of the channels. The unitized design of the

Secure Vent components will engage and seal

both the inner and outer pipe elements with the

same procedure. Sealant and securing screws

are not required.

E. Attach vent components to each other - Other

vent sections may be added to the previously

installed section in accordance with the require-

ments of the vent tables. To add another vent

component to a length of vent run, align the

dimpled end of the component over the inclined

channel end of the previously installed section,

adjusting the radial alignment until the four lock-

ing dimples are aligned with the inlets of the four

incline channels of the previous section. Push

the vent component against the previous section

until it fully engages, then twist the component

clockwise running the dimples down and along

the incline channels until they seat at the end of

the channels.

This seating position is indicated

by the alignment of the arrow and dimple as

shown in Figure 16 on Page 14.

F. Install firestop/spacer at ceiling -

When using Secure Vent, use SV4.5VF firestop/

spacer at ceiling joists; when using Secure Flex,

use SF4.5VF firestop/spacer. If there is living

space above the ceiling level, the firestop/

spacer must be installed on the bottom side of

the ceiling. If attic space is above the ceiling, the

firestop/ spacer must be installed on the top side

of the joist. Route the vent sections through the

framed opening and secure the firestop/spacer

with 8d nails or other appropriate fasteners at

each corner.

Figure 26

Ceiling

Fireplace

Vertical

Rise

SV4.5 HT-2

Termination

Shown

Support Bracket Spacing

Every 5 ft (1.52 m)

SV4.5 HT-2

Termination

Shown

Support Brackets

Building

Support

Framing

Horizontal / Inclined Run

SV4.5E90

Elbow

See Figure 17 on Page 14 for vertical

vent section support.

u

When Using Secure Flex,

Use Firestop / Spacer SF4.5VF

u

Firestop / Spacer

SV4.5VF

SV4.5L6/12/24/6/48

Vent Sections

Exterior

Wall

Advertising
This manual is related to the following products: