Warning – Lennox Hearth ADAGIO-MP User Manual

Page 19

Advertising
background image

19

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

H

V

Wall Firestop/Spacer

(SV4.5HF)

When using Secure Flex,

use Firestop/Spacer

SF4.5VF.

Ceiling

Firestop/Spacer

(SV4.5VF)

When using Secure Flex,

use Firestop/Spacer

SF4.5HF.

Figure 29

- Top Vent -

ONE 90 DEGREE ELBOW - ELBOW CONNECTION AT APPLIANCE

See Table 7 as an aid in venting component selection for a particular

range of exterior wall thicknesses.

See Table 7 as an aid in venting component selection for

a particular range of exterior wall thicknesses.

H

Wall

Firestop/Spacer

(SV4.5HF)

V

When using Secure Flex,

use Firestop/Spacer

SF4.5HF

Notes:

• Secure Vent™ components (rigid vent pipe and terminal) are shown

in the Figures; Secure Flex™ components (flexible vent pipe and

terminal) may also be used.

Two 45 degree elbows may be used in place of one 90 degree elbow.

The same rise to run ratios, as shown in the venting Figures for 90

elbows, must be followed if 45 degree elbows are used.

SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be

used anytime vent pipe passes through a combustible floor or ceiling.

SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must

be used anytime vent pipe passes through a combustible wall.

• It is very important that the horizontal/inclined run be maintained

in a straight (no dips) and recommended to be in a slightly elevated

plane, in a direction away from the fireplace of 1/4" rise per foot (20

mm per meter) which is ideal, though rise per foot run ratios that are

smaller are acceptable all the way down to at or near level.

The tables show a 1(V) to 5(H) ratio up to a maximum horizontal run

of 20 feet except for installations where an elbow is the only vertical

vent section in the system (see Figure 29).

• AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT

WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE

SYSTEM. See Figure 29.

See Table 7 as an aid in venting component selection for a particular

range of exterior wall thicknesses.

WARNING

Under no circumstances, may separate sections of

concentric flexible vent pipe be joined together.

HORIZONTAL VENT FIGURES/TABLES

Figure 30

-

Top Vent - ONE 90 DEGREE ELBOW -

ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE

Square termination

(SV4.5HT-2) shown.

Square termination

(SV4.5HT-2) shown.

Example: If 20 feet of (H) hori-

zontal vent run is needed, then

4 feet minimum of (V) vertical

vent will be required.

This table shows a 1(V) to

5(H) ratio. For every 1 foot of

vertical, you are allowed 5 feet

of (H) horizontal run up to a

maximum (H) horizontal run

of 20 feet.

Venting Components Required for Various Exterior Wall Thick-

nesses, when using Square Termination Kit (SV4.5HT-2)

Vent Components Required Exterior Wall Thickness - inches (mm)
Termination Kit Only

6 to 9-1/4 (152 to 235)

Termination Kit and 6 In. Vent

Section (SV4.5L6)

10-3/4 to 14 (273 to 356)

Termination Kit and 12 in.

Vent Section (SV4.5L12)

16-3/4 to 20 (426 to 508)

Termination Kit and Tele-

scopic Section (SV4.5L12)

11-3/4 to 20 (299 to 508)

Table 7

Note: See Figure 28 showing wall thickness range

when using SV4.5HT-2 termination kit only.

Table C

H Maximum

V Minimum

feet

(meter)

feet

(meter)



(0.914)

Elbow Only

Table D

H Maximum

V Minimum

feet

(meter)

feet

(meter)

5

(1.524)

1

(0.05)

10

(.048)

2

(0.610)

15

(4.572)



(0.914)

20

(6.096)

4

(1.219)

V + H = 40 feet (12.2 m) Max.

H = 20 feet (6.096 m) Max.