NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

29

* Vent to combustible

on Side = 1" Min.

Vent to combustible

on Top = 3" Min.

IMPORTANT NOTE:

Place the header verti-

cal as shown to main-

tain proper clearance

from the vent system to

combustibles.

Figure 52

Fireplace (right side)

1" Min.

(25 mm)*

4" Min

(102 mm)*

This Area Must

Remain Clear of

Combustible Materials

Top of

Appliance

Header

(2x4)

Drywall

Spacers

FINISHING REQUIREMENTS - Wall Details

Complete finished interior wall. To install the appliance facing flush with

the finished wall, position framework to accommodate the thickness of

the finished wall (Figure 52).

u

4" clearance is required above the elbow for installations that require an

elbow at the top of the unit and that ends in a horizontal termination.

Hearth Extension

A hearth extension is not required with this appliance. If a hearth extension

is used, do not block the lower control compartment panel. Any hearth

extension used is for appearance only and does not have to conform to

standard hearth extension installation requirements.

Note: Combustible wall finish materials and/or surround materials must not

be allowed to encroach the area defined by the appliance front face (black

sheet metal). Never allow combustible materials to be positioned in front of

or overlapping the appliance front face.

Non-combustible materials, such as surrounds and other appliance trim,

may be installed on the appliance front face with these exceptions: they must

not cover any portion of the glass or the air gaps above the glass door.

Vertical installation clearances to combustible mantels vary according

to the depth of the mantel. Mantels constructed of non-combustible

materials may be installed above the appliance opening as outlined in

Figure 3 on Page 6.