This button controls output power to connected load(s) and has

three functions:

• ON
• Alarm Silence
• Manual Battery Test

ON - Pressing this button will start up the UPS in order to

provide conditioned and protected power.
Alarm Silence - To silence alarms, press this button for at least

one second. After the alarm is silenced, the UPStation GXT 2U

will reactivate the alarm system to alert of additional problems.

Manual Battery Test - To initiate a manual battery test,

press the ON button for at least one second while operating

from utility power with no alarm conditions present.
• If only three of the five Battery LEDs illuminate, allow the

UPS to recharge the batteries for 24 hours.

• After 24 hours, retest the batteries.
• After the batteries have been retested, if only three of the

five Battery LEDs illuminate, contact your local dealer, Lie-

bert representative or Liebert Worldwide Support Group.

NOTE
The LOW BATTERY and BYPASS reminder alarms

CANNOT be silenced.