0 communications, 1 communications interface port, Ommunications – Liebert GXT 2U User Manual

Page 23: Communications interface port

Advertising
background image

Communications

19

7.0

C

OMMUNICATIONS

7.1

C

OMMUNICATIONS

I

NTERFACE

P

ORT

The UPStation GXT 2U UPS has a standard DB-9 serial port female

connector located on the rear of the UPS unit. Several signals are pro-

vided on this port and are assigned as follows:

* Maximum voltage and current on pins 1, 7, 8, and 9 is 60VDC; 10.0 mA.

Pin

Assignment Description

1

Low Battery (open collector)

2

UPS TxD (typical RS-232 levels)

3

UPS RxD (typical RS-232 levels)

4

Remote Shutdown (5-12VDC, 10-24 mA max); battery operation

5

Common

6

Remote Shutdown (short to pin 5); all modes of operation

7

Low Battery (open emitter)

8

Utility Fail (open emitter)

9

Utility Fail (open collector)

Pin Assignment

Collector to Emitter*

5

4

3

2

1

6

7

8

9

(-)

(+)

330 Ohms

Open
Collector

Open
Emitter