0 troubleshooting, Roubleshooting, 0 - troubleshooting – Liebert GXT 2U User Manual

Page 31

Advertising
background image

Troubleshooting

27

10.0 T

ROUBLESHOOTING

The information below indicates various symptoms a user may

encounter in the event the UPStation GXT 2U develops a problem.

Use this information to determine whether external factors caused the

problem and how to remedy the situation.
1. The Fault indicator will illuminate, indicating the UPS detected a

problem.

2. An alarm will sound, alerting that the UPS requires attention.
3. One or more additional load/battery level LED indicators will be illu-

minated to provide a diagnostic aid to the operator, as described below:

LED status

Diagnosis / Audible alarm

All LEDs

On bypass due to output overload; beep every half-second

A LED

On bypass due to overtemperature condition; beep every 4 sec.

B LED

On bypass due to DC bus overvoltage; beep every 4 sec.

C LED

On bypass due to control power supply failure; beep every 4 sec.

D LED

On bypass due to PFC failure; beep every 4 sec.

E LED

On bypass due to inverter failure; beep every 4 sec.

A&C LEDs

UPS failed battery test; long beep every minute

C&E LEDs

UPS shutdown due to command from communication port

(SNMP); no beep

Battery LED

Flashing

Internal Battery source not available (continuous horn). Check

battery connection, completely power down and reboot UPS.

AC LED

Flashing

Line-to-neutral reversal in the AC input power supply or a loss of

proper grounding; continuous horn and UPS will not start.

Bypass LED

Flashing

Utility power voltage or frequency is out of tolerance; bypass is

unavailable.

This example shows the UPS

on bypass due to output overload.

Fault

E

D

C

B

A

A

B

C

D

E

Fault

AC INPUT BATTERY UPS ON BYPASS

BATTERY

UPS ON

BYPASS

AC

INPUT

LOAD/BATTERY

LEVEL INDICATORS