Liebert GXT 2U User Manual

Page 33

Advertising
background image

Troubleshooting

29

Fault and Bypass

indicator LEDs

and all load level

LEDs are

illuminated.

UPS overloaded or load

equipment is faulty.

Check load level display

and remove non-essential

loads. Recalculate the load

and reduce number of

loads connected to UPS.

Check load equipment for

faults.

Fault and Bypass

indicator LEDs

and diagnostic

LED A are

illuminated.

UPS internal fan has a

problem or UPS shutdown

due to temperature

condition. Load is on

bypass power.

Ensure UPS is not

overloaded, ventilation

openings not blocked, or

room ambient temperature

is not excessive. Wait 30

minutes to allow UPS to

cool, then restart UPS. If

UPS does not restart,

contact your local dealer,

Liebert representative or

the Liebert Worldwide

Support Group.

Fault and Bypass

indicator LEDs

and diagnostic

LED B are

illuminated.

UPS internal DC bus

overvoltage.

UPS requires service.

Contact your local dealer,

Liebert representative or

the Liebert Worldwide

Support Group.

Fault and Bypass

indicator LEDs

and diagnostic

LED C are

illuminated.

UPS control power supply

fault.

UPS requires service.

Contact your local dealer,

Liebert representative or

the Liebert Worldwide

Support Group.

Fault and Bypass

indicator LEDs

and diagnostic

LED D are

illuminated.

UPS PFC (Power Factor

Correction Circuit) fault.

UPS requires service.

Contact your local dealer,

Liebert representative or

the Liebert Worldwide

Support Group.

Fault and Bypass

indicator LEDs

and diagnostic

LED E are

illuminated.

UPS inverter fault.

UPS requires service.

Contact your local dealer,

Liebert Representative or

the Liebert Worldwide

Support Group.

Fault indicator

LED and

diagnostic LED A

and C are

illuminated.

UPS failed the battery test.

Replace batteries. Contact

your local dealer, Liebert

representative or the

Liebert Worldwide Support

Group.

Table 1

Troubleshooting guide (continued)