During normal operation,

utility power provides energy

to the UPS. The filters, power

factor correction circuit and

the inverter process this

power to provide computer

grade power to connected

loads. The UPS maintains

the batteries in a fully

charged state.
The four green load level LEDs indicate an approximate level of load

in 25% increments. If the UPS becomes loaded beyond full rating, the

fifth (amber) LED indicator will illuminate and the UPS will sound an

audible alarm. The display template indicates the percentage of load

(26-50% of load shown in the example above) on the UPS output.

6.2

B

YPASS

M

ODE

O

PERATION

Bypass mode occurs when

the OFF button is pressed

once while the UPS is in

Normal Mode. During bypass

operation, utility power

provides energy to the UPS.

The utility power bypasses

the inverter and provides

power for the connected load.
The four green load level LEDs indicate an approximate level of load

in 25% increments. If the UPS becomes loaded beyond full rating, the

fifth (amber) LED indicator will illuminate and the UPS will sound an

audible alarm. The display template indicates the percentage of load

(26-50% of load shown in the example above) on the UPS output.

!

CAUTION

Turning OFF the UPS while in bypass mode will result in loss

of output power.