2 standby / manual bypass button, 3 load/battery level indicators (4 green, 1 amber), 4 fault indicator led (red) – Liebert GXT 2U User Manual

Page 19: 5 bypass indicator led (amber), 6 ups on indicator led (green), 7 battery indicator led (amber), Standby/manual bypass button, Load/battery level indicators (4 green, 1 amber), Fault indicator led (red), Bypass indicator led (amber)

Advertising
background image

Controls and Indicators

15

5.2

S

TANDBY

/M

ANUAL

B

YPASS

B

UTTON

This button controls output power to connected load(s) and has

dual functions: Standby and Manual Bypass.

5.3

L

OAD

/B

ATTERY

L

EVEL

I

NDICATORS

(4 G

REEN

, 1 A

MBER

)

The load/battery level indicators have dual functions. During normal

mode operation LED indicators display the approximate electrical

load placed upon the UPS; and during battery mode operation LED

indicators display approximate battery capacity.
The UPStation GXT 2U is equipped with automatic and remote bat-

tery test features. The automatic test occurs every 14 days (this option

is user configurable) if utility has not been interrupted. Should the

battery fail this test, the red Fault indicator LED along with the A and

C diagnostic LEDs will illuminate and an alarm will sound (refer to

10.0 - Troubleshooting). The remote test feature functions with

MultiLink 3 software and can remotely initiate the battery test.

5.4

F

AULT

I

NDICATOR

LED (R

ED

)

The Fault indicator LED is illuminated if the UPS has detected a

problem. Also, one or more of the load/battery level indicators may be

illuminated (refer to 10.0 - Troubleshooting).

5.5

B

YPASS

I

NDICATOR

LED (A

MBER

)

The Bypass indicator LED is illuminated when the UPS is operating

from bypass power. An alarm will sound indicating the UPS detected

a problem, or the manual bypass function has been activated.

5.6

UPS ON I

NDICATOR

LED (G

REEN

)

The UPS ON indicator LED is illuminated when the UPS inverter is

operating and supplying power to your connected loads.

5.7

B

ATTERY

I

NDICATOR

LED (A

MBER

)

The Battery indicator LED is illuminated when the UPS is operating

on battery.

!

CAUTION

While the UPS is in Normal Mode operation, pressing

the Standby/ Manual Bypass button once will put the

UPS into Bypass Mode.
Once the UPS is in Bypass Mode operation, press the

Standby/ Manual Bypass button two distinct times (for

about one second each time) to turn off the UPS.

Perform all necessary shutdown procedures on

connected loads before turning off the UPS.

Advertising