1. Pin 6 of the 9-pin communication connector is used for “Any-Mode

Shutdown” of the UPS output. This control input may be used in

special applications to disable the UPS output power—both

Inverter and Bypass.

2. The Options tab allows the behavior of the Any-Mode Shutdown

feature to be modified. When the program opens, or the REFRESH

button is pressed, the UPS setting is read by the configuration

program and displayed.

7.3.1 Auto-Enable Output

7.3.2 Pin 6 Logic

If version 1.6 (or later) is used with an earlier GXT 2U model (with an

earlier UPS firmware version), the Any-Mode Shutdown features can-

not be changed.
If the configuration program is used with an earlier UPS model (with

an earlier UPS firmware version) that does not support the modifica-

tion of these settings, the Options tab will display a reminder of the

factory default settings. These cannot be changed.

!

WARNING

Note that when this option is selected and the UPS output is

disabled using Pin 6, the UPS output can turn on

automatically and without warning if the Pin 6 connection is

changed.

!

WARNING

DO NOT CHANGE THIS OPTION from the factory default

setting unless you are ready to install a normally-closed

connection between Pins 5 & 6. This connection must be

maintained to use the UPS or to use the configuration

program again, including the ability to change the UPS

setting back to the default setting using the configuration

program via a serial communication link.